kVA to Amps, Breaker & Feeder Calculator (3-Phase / 1-Phase)

Compute full-load current (FLA), continuous 125% OCPD breaker sizing, active kW, reactive kVAR, and 75°C copper cable sizes across 120V to 13.8kV systems.

How to Convert Three-Phase & Single-Phase kVA to Full-Load Amps

Transformers, standby diesel generators, and industrial uninterruptible power supplies (UPS) are rated in kilovolt-amperes (kVA) rather than kilowatts (kW) because internal copper winding losses (I²R) and core heating depend on total apparent current regardless of load power factor. On a single-phase circuit, full-load current equals apparent power in volt-amperes divided by line voltage: I = (kVA × 1000) / V.

On a balanced three-phase distribution bus (such as 208 V commercial wye, 400 V IEC/VDE industrial wye, or 480 V NEC plant switchgear), phase currents are displaced by 120 electrical degrees, introducing the square root of three (√3 ≈ 1.73205) into the denominator: I = (kVA × 1000) / (1.732 × V_LL). For example, a standard 75 kVA dry-type transformer draws 90.21 A on its 480 V primary and 208.18 A on its 208Y/120 V secondary.

NEC 450.3(B) Overcurrent Protection & 75°C Feeder Lug Termination Rules

Under NFPA 70 (NEC Table 450.3(B) for transformers rated 1000 V or less with primary currents of 9 A or more) and continuous feeder rule NEC 215.3, primary overcurrent protective devices (OCPD) and secondary feeder conductors are typically sized at 125% of full-load current. Where 125% of transformer current does not correspond to a standard NEC 240.6(A) circuit breaker or fuse rating, Note 1 to Table 450.3(B) permits rounding up to the next higher standard rating.

Pursuant to NEC 110.14(C)(1), circuit breaker and transformer lugs on equipment rated above 100 A (or marked 75°C) require selecting conductor ampacity from the 75°C column of NEC Table 310.16—even when pulling 90°C THHN/THWN-2 or XHHW-2 wire—unless ambient temperature and conduit fill derating require using the 90°C starting value.

Reference Benchmark & Formula Specification

Deterministic formula: I_3Ø = (kVA × 1000) / (1.732 × V_LL) | I_1Ø = (kVA × 1000) / V_LN | OCPD = 1.25 × FLA

Architecture / Standard Tier Specification Scope / Operating Range Reference Benchmark
45 kVA Dry-Type 3Ø 480 V Primary -> 208Y/120 V Secondary 54.1 A Pri / 124.9 A Sec 70 A Pri / 175 A Sec OCPD
75 kVA Dry-Type 3Ø 480 V Primary -> 208Y/120 V Secondary 90.2 A Pri / 208.2 A Sec 125 A Pri / 300 A Sec OCPD
250 kVA IEC Cast-Resin 3Ø 20 kV Primary -> 400Y/230 V Secondary 7.2 A Pri / 360.8 A Sec 400 A / 450 A LV ACB
500 kVA Substation 3Ø 13.8 kV Primary -> 480Y/277 V Secondary 20.9 A Pri / 601.4 A Sec 800 A LV Main Breaker

Frequently Asked Questions

Does power factor (cos φ) change the full-load amps of a kVA rating?

No. Because kVA already represents total apparent power (S = V × I × √3), full-load current depends solely on kVA and system voltage. Power factor determines how much of that kVA converts into usable real power (kW = kVA × cos φ) versus magnetizing reactive power (kVAR).

How many amps is a 75 kVA transformer at 480V and 208V three-phase?

At 480V three-phase, a 75 kVA transformer draws 90.21 A full-load (requiring a 112.8 A -> 125 A primary breaker at 125%). On a 208V three-phase secondary, it delivers 208.18 A full-load (260.2 A at 125%, typically protected at 250 A or 300 A per NEC 240.4(B) / 450.3(B)).

When should I select 100% instead of 125% breaker sizing?

Use 125% for continuous loads operating 3 hours or more (NEC 215.2 / 210.20) and NEC 450.3(B) primary-only transformer protection. Select 100% when evaluating nominal IEC 60076 nameplate current or listed 100%-rated electronic trip switchgear assemblies.